Welcome to the Elevator Association of Florida Website! 


Elevator Association of Florida

 

Home
Members
Officers & Board
Meetings & Events
News & Announcements
Bureau Q & A
Meeting Minutes
Contact Us
Links

 

 

Elevator Association of Florida

 

 

 

 

 

 

 
 
April 2004 Questions & Answers

 

 Q & A Archives:
[January 2004 Q & A] [April 2004 Q & A] [July 2004 Q & A] [October 2004 Q & A] [January 2005 Q & A]
 


Questions Submitted to the Bureau of Elevator Safety for the
April 2004 Elevator Association of Florida meeting –
including the Bureau’s answers


Question 1:  An enforcing agency inspecting elevators is referencing NFPA-70, 2002 Edition rather than the State mandated NFPA-70, 1999. I understood that a more stringent code is acceptable, but I also understand that the inspector or, in this case, the contracted agency, had no right to pick the code arbitrarily without an ordinance adopting the more stringent standard. Is this true? 

Answer:  According the Florida Statutes Chapter 553.791(14) no local enforcement agency, local building official, or local government may adopt or enforce any laws, rules, procedures, or standards more stringent than those prescribed by this section. The Fire Marshal’s Office is the authority having jurisdiction for this matter.

Question 2:  Broward County Elevator Inspectors are giving elevator owners the choice of removing sump pumps or buying and installing oil/water separators.

a) A17.l Rule 106.1 clearly says elevators must have a drain or a sump pump.
b) 61C-5.001(7)( e) clearly says elevators may have sump pumps.

Most owners will remove pumps rather than spend 10 to 30 thousand dollars for a separator. This leaves elevator pits, which have had pumps removed, full of water, which is extremely dangerous.

Is Broward County allowed to set environmental issues above the elevator safety issues addressed by our code? Or is there, perhaps, another agency which should worry about oil/water separation? Chapter 61C-5 removed the requirement for a pump because all elevators plainly do not need pumps. I'm sure our legislators did not intend to place elevator repair personnel, inspectors, and the riding public in jeopardy.

Broward County is inspecting to a less stringent code standard by causing these pumps to be removed and should cease doing so. Please respond as to whether Broward County has the authority to require the removal of sump pumps if separators are not installed.

Answer:  The Division is researching this issue with Broward County to make sure that there are no conflicts between the statute or law, the rules, and practical policy. After our research is complete, the Division will do whatever the Law states and will communicate our findings to the Elevator Association.

Question 3:  ASME A17.1 Rule 211.3b was revised with the 1997 edition, changing the requirement for smoke detectors for recall to "automatic fire initiating devices" and removed the words "except at unenclosed landings". This rule requires such devices to be installed in elevator spaces and at each elevator floor "in compliance with NFPA-72" (National Fire Alarm Code). An exception in NFPA-72 allows the use of heat detectors for recall in unenclosed lobbies where smoke detectors are not feasible.

As the local Fire Marshal is the enforcing authority for NFPA-72, if they grant a variance or exception in writing from NFPA-72 removing the requirement for automatic fire initiating devices for elevator recall in open air (unenclosed) lobbies, will the Bureau of Elevator Safety accept the exception and allow these devices to be eliminated?

Answer:  The State Fire Marshal’s office has been made aware of this issue and is currently addressing the life safety 101 and the NFPA 72 harmonization.

Question 4:  The State monitors are citing "Code Data Plates" which are to state the Edition of the Code that was in effect when the elevator was installed or altered. This rule was first adopted by A17.1 with the 1996 Edition, but is being cited on all existing units.

As the state has not enforced any retroactive codes per Chapter 399.03(7) and 399.03(8), should this rule be cited for elevators installed or altered prior to 10/04/00, the effective date of the 1996 Edition of A17.1?

Answer:  According to the ASME A17.1-1996 edition (inquiry 01-07, subject Rule 1206.1I, Code Data Plate) Question: Is it the intent of the A17.1 Code to require that all existing elevators be provided with a Code Data Plat the answer is yes. The A17 Committee approval date is June 27, 2001.

We are presently reviewing how this will be implemented.

Question 5:  I understand that an "alteration" inspection will not count as an "inspection" so that if an alteration inspection takes place when an inspection is due, two inspection reports have to be filled out for the same inspection, one for the alteration and one for the annual inspection. Please clarify this procedure.

Answer:  Only routine inspection reports meet the requirement for a current satisfactory inspection as required by FS 399.07(1). When a routine inspection report is submitted, ASME A17.1 rules 1001, 1004, 1007 inspections have been performed. If an alteration is performed only the appropriate parts of section 1200 MAY have been inspected and not the entire conveyance.


Download Q & A - PDF Format

 

   

 
Copyright© 2005-2008 Elevator Association of Florida, Inc.,
All Rights Reserved.  Last Updated 3/13/08.
Email: info@fla-elevator-association.org